BCB-EX
Battery circuit breaker box
Explosion proof battery circuit breaker box, suitable for zone 1 and 2 gas hazardous areas where hydrogen (H2) may be present.
Key features
- Over current and short circuit protection
- Battery disconnect facility for maintenance
- Remote trip facility and black start override (optional)
Standards/certification
- NEN/EN/IEC 61892 Electrical installations on Mobile and fixed offshore units
- EN 60079-0, EN 60079-1, EN 60079-7
- KEMA 02ATEX2103X; ATEX II 2 G Ex d(e) IIB+H2 T6
- IEC 60079-0, IEC 60079-1, IEC 60079-7
- KEM 09.0089X; Ex d(e) IIB+H2 T6
Electrical characteristics
- Circuit breaker up to 1200A, MCB or MCCB (controllable through enclosure front, pad lockable)
- Cable connection terminals: customizable
Physical characteristics
- Wall or floor mounted suitable for indoor or outdoor location
- Cast light alloy (offshore coated) or stainless steel Ex-d enclosure
- Stainless steel 316L Ex e connection box (optional)
- RAL7035 (Light Grey) Orga offshore coating (client specific coating on request)
- Dimensions and weight: Depending on customisable options
- Provided with bottom cable entries
- Degree of protection: IP66
System design, control and monitoring (By customisation)
- Output contact (potential free) for:
- Circuit breaker trip status
- Override status contact
- Battery low / low-low voltage alarm contact
- Circuit breaker shunt trip by:
- 24V signal
- Voltage free contact
- Battery low voltage monitor
- ESD / Black start override by key operated switch
- Override on indicator (red) on front of enclosure
- Battery low voltage indicator (yellow) on front of enclosure